Specialist electrical and industrial automation store
فارسی

Flow sensor ifm model SV4204

Flow sensor ifm model SV4204,  Part number SV4204

Check the part number and technical specifications before selection; an image alone is not sufficient for matching.

Manufacturer part number
SV4204
Manufacturer
ifm
ARAN VISION part number
AV-FEED-GE14NV
Product description
Flow sensor ifm part number SV4204; Number of inputs and outputs: Number of analogue outputs: 2; Measuring range: 1...20 l/min: 0.06...1.2 m³/h; Process connection: threaded connection G 1/2 internal thread DN8. Technical specifications, condition and supply feasibility are checked before ordering.
Manufacturer standard lead time
Manufacturer confirmation required

Manufacturer replenishment time; delivery to you is confirmed separately.

Product attributes

Number of inputs and outputs
Number of analogue outputs: 2
Measuring range
1...20 l/min: 0.06...1.2 m³/h
Process connection
threaded connection G 1/2 internal thread DN8
Special feature
Gold-plated contacts
Application
for industrial applications
Media
water; glycol solutions; coolants
Medium temperature [°C]
-10...90
Pressure rating
12 bar: 1.2 MPa
Note on pressure rating
up to 40 °C
MAWP for applications according to CRN [bar]
3.9
Operating voltage [V]
18...30 DC
Current consumption [mA]
< 30
Min. insulation resistance [MΩ]
100; (500 V DC)
Protection class
III
Reverse polarity protection
Yes
Power-on delay time [s]
< 3
Measuring principle
Vortex
Total number of outputs
2
Output signal
analogue signal
Number of analogue outputs
2
Analogue current output [mA]
4...20
Max. load [Ω]
500
Short-circuit protection
Yes
Overload protection
Yes
Display range
0...24 l/min: 0...1.44 m³/h
Resolution
0.1 l/min: 0.005 m³/h
Analogue start point ASP
0...16 l/min: 0...0.96 m³/h
Analogue end point AEP
4...20 l/min: 0.24...1.2 m³/h
In steps of
0.1 l/min: 0.005 m³/h
Measuring dynamics
1:20
Measuring range [°C]
-10...90
Display range [°C]
-30...110
Resolution [°C]
0.5
Analogue start point [°C]
-10...70
Analogue end point [°C]
10...90
In steps of [°C]
0.5
Accuracy (in the measuring range)
± 2 % MEW; (water)
Repeatability
± 0,5 % MEW
Accuracy [K]
± 1
Response time [s]
1; (dAP = 0)
Damping process value dAP [s]
0...5
Dynamic response T05 / T09 [s]
T09 = 6
Parameter setting options
Damping for the analogue output dAA; Display unit
Ambient temperature [°C]
0...60
Note on ambient temperature
medium temperature < 80 °C; medium temperature < 90 °C: 0...50 °C
Storage temperature [°C]
-20...80
Protection
IP 65; IP 67
EMC
DIN EN 61000-6-2; DIN EN 61000-6-3
CPA approval
model number: 001VO; accuracy class: -; maximum allowable error: ± 2 % FS; Q (min): 0,09 m³/h; Q (t): 0,24 m³/h; Q (max): 1,2 m³/h
Shock resistance
DIN EN 60068-2-27: 5 g (11 ms)
Vibration resistance
DIN EN 60068-2-6: with water / 10...50 Hz 1 mm; with water / 50...2000 Hz 2 g
MTTF [years]
342
UL approval
UL approval no.: I002
Pressure Equipment Directive
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight [g]
439.5
Housing
rectangular
Dimensions [mm]
110 x 45 x 72
Materials
stainless steel (316L/1.4404); PC; PBT+PC-GF30; PPS; TPE-U
Materials (wetted parts)
stainless steel (316L/1.4404); ETFE; PA 6T; PPS; FKM
Tightening torque [Nm]
30
Display
colour display 1,44", 128 x 128 pixels; 2 x LED, yellow
Remarks
MW = measured value; MEW = Final value of the measuring range
Pack quantity
1 pcs.
Connector
1 x M12; coding: A; Contacts: 4, gold-plated
Report a product information error
Documents and technical resources
ARAN VISION product sheetView and print specifications
Manufacturer datasheetOpen manufacturer datasheet
Official product pageifm

Source checked: 2026-09-10

Product questions

Send the part number and your question to support to check compatibility, lead time or specifications.

Additional information and order matching

The revision, condition, delivery time and required documentation must be confirmed before the order is finalised. Export classifications and approvals are provided only where valid evidence is available.

Authenticity and condition

Product authenticity and actual condition, including new condition when offered as new, are checked before final approval and recorded in the quotation.

Matching technical version

The part number, revision, firmware or version is checked against your requirements. Apparently similar products may differ in price because of their version or condition.

Delivery estimate before ordering

Specialist products have a lead time. The valid delivery estimate is stated in the quotation after checking availability and specifications.

Technical code verification

Model, revision and equipment compatibility are checked before final confirmation.

Clear product condition

New, surplus or refurbished condition and warranty terms are stated in the quotation.

Products outside the catalog

If this model is unavailable, send the part number or nameplate photo for custom sourcing.

Related products