ARAN VISIONAccountQuote basketفارسی

ifm SA6014

ifm SA6014
Manufacturer
ifm
Manufacturer part number
SA6014
Description
Flow sensor, SAN12XDB50KG/US-100
Manufacturer standard lead time
Manufacturer confirmation required; not a guaranteed delivery date.

Product specifications

Number of inputs and outputs
Number of analogue outputs: 2
Process connection
threaded connection 1/2" NPT external thread
Special feature
Gold-plated contacts
Media
water; glycol solutions; air; oils
Note on media
low-viscosity oils with viscosity: ≤ 40 mm²/s (104 °F); high-viscosity oils with viscosity: > 40 mm²/s (104 °F)
Medium temperature [°F]
-4...194
Pressure rating
100 bar: 1450 psi: 10 MPa
MAWP for applications according to CRN [bar]
100
Operating voltage [V]
18...30 DC
Current consumption [mA]
< 100
Protection class
III
Reverse polarity protection
yes
Power-on delay time [s]
10
Measuring principle
calorimetric
Total number of outputs
2
Output signal
analogue signal
Number of analogue outputs
2
Analogue current output [mA]
4...20; (scalable)
Max. load [Ω]
350
Short-circuit protection
yes
Type of short-circuit protection
pulsed
Overload protection
yes
Probe length L [mm]
26.6
Operating mode
relative; absolutely liquid; absolutely gaseous; (absolute: reference measurement recommended; Factory setting: relative)
Resolution [ft/s]
0.05
Analogue start point ASP [ft/s]
0...7.95
Analogue end point AEP [ft/s]
1.9...9.85
Resolution [ft/s]
2
Analogue start point ASP [ft/s]
0...264
Analogue end point AEP [ft/s]
64...328
Measuring range [°F]
-4...194
Resolution [°F]
0.5
Analogue start point [°F]
-4...169
Analogue end point [°F]
39...212
In steps of [°F]
0.5
Setting range [ft/s]
0...9.85
Greatest sensitivity [ft/s]
0.15...9.85
Setting range [ft/s]
0...19.5
Setting range [ft/s]
6...328
Greatest sensitivity [ft/s]
6...328
Setting range [ft/s]
6...656
Temperature drift [cm/s x 1/K]
0,01 fps x 1/K (< 68 °F; > 158 °F)
Temperature gradient [K/min]
100
Repeatability
0,05 m/s; (water; flow velocity: 0,05...3 m/s)
Accuracy
± (7 % MW + 2 % MEW); (for relative mode in the range of maximum sensitivity under the following conditions:; water: 68...158 °F; inlet length: 5 ft; DN25 (DIN 2448); mounting position according to instructions; Accuracy can differ for other media and mounting positions.)
Temperature drift
± 0,003 K/°F
Accuracy [K]
± 0,3 / ± 1; (water; flow velocity: 1...9,85 fps / air; flow velocity: > 32,8 fps)
Response time [s]
0.5; (T09; water; glycol: 0,8 s; air: 7 s; oil: 1,8 s; each T09)
Dynamic response T05 / T09 [s]
1,5 (T09); (water; flow velocity: 1...9,85 fps)
Parameter setting options
medium selection; Damping; Teach function; display can be rotated and switched off; standard unit of measurement; process value colour
Ambient temperature [°F]
-40...176
Storage temperature [°F]
-40...212
Protection
IP 65; IP 67
EMC
DIN EN 60947-5-9
Shock resistance
DIN EN 60068-2-27: 50 g (11 ms)
Vibration resistance
DIN EN 60068-2-6: 20 g (10...2000 Hz)
MTTF [years]
180
UL approval
UL approval no.: I004; File number UL: E174189
Weight [g]
268
Housing
cylindrical
Dimensions [mm]
Ø 34 / L = 133.4
Materials
stainless steel (316L/1.4404); stainless steel (301/1.4310); PBT-GF20; PBT-GF30
Materials (wetted parts)
stainless steel (316L/1.4404)
Probe diameter [mm]
5
Installation length EL [mm]
26.6
Display
Display unit: 6 x LED, green (%, fps, gpm, cfm, °F, 10³); measured values: alphanumeric display, red/green 4-digit
Remarks
MW = measured value; MEW = Final value of the measuring range
Pack quantity
1 pcs.
Connector
1 x M12; coding: A; Contacts: 4, gold-plated

Documents and media

Price and availability

Checking member pricing…

Supply, condition, exact revision and delivery are confirmed before accepting the order. Catalog presence does not mean local stock.