Specialist electrical and industrial automation store
فارسی

Flow sensor ifm model SM6621

Flow sensor ifm model SM6621,  Part number SM6621

Check the part number and technical specifications before selection; an image alone is not sufficient for matching.

Manufacturer part number
SM6621
Manufacturer
ifm
ARAN VISION part number
AV-FEED-10N8UZD
Product description
Flow sensor ifm part number SM6621; Number of inputs and outputs: Number of digital outputs: 2; Number of analogue outputs: 1; Measuring range: 0.05...35 l/min: 0.003...2.1 m³/h: 0.6...555 gph: 0.01...9.25 gpm; Process connection: threaded connection 1/2" NPT internal thread DN15. Technical specifications, condition and supply feasibility are checked before ordering.
Manufacturer standard lead time
Manufacturer confirmation required

Manufacturer replenishment time; delivery to you is confirmed separately.

Product attributes

Number of inputs and outputs
Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
0.05...35 l/min: 0.003...2.1 m³/h: 0.6...555 gph: 0.01...9.25 gpm
Process connection
threaded connection 1/2" NPT internal thread DN15
Special feature
Gold-plated contacts
Media
conductive liquids; water; hydrous media
Note on media
conductivity: ≥ 20 µS/cm; viscosity: < 70 mm²/s (40 °C)
Medium temperature [°F]
-4...194
Pressure rating
16 bar: 1.6 MPa
Operating voltage [V]
18...30 DC; (to SELV/PELV)
Current consumption [mA]
< 80
Protection class
III
Reverse polarity protection
Yes
Power-on delay time [s]
5
Measuring principle
magnetic-inductive
Inputs
counter reset
Total number of outputs
2
Output signal
switching signal; analogue signal; pulse signal; IO-Link; frequency signal; (configurable)
Electrical design
PNP/NPN
Number of digital outputs
2
Output function
normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]
2
Permanent current rating of switching output DC [mA]
100
Number of analogue outputs
1
Analogue current output [mA]
4...20; (scalable)
Max. load [Ω]
500
Pulse output
flow rate meter
Short-circuit protection
Yes
Type of short-circuit protection
pulsed
Overload protection
Yes
Display range
-42...42 l/min: -2.5...2.5 m³/h: -666...666 gph: -11.1...11.1 gpm
Resolution
0.02 l/min: 0.002 m³/h: 0.6 gph: 0.01 gpm
Set point SP
0.25...35 l/min: 0.015...2.1 m³/h: 4.2...555 gph: 0.07...9.25 gpm
Reset point rP
0...34.8 l/min: 0...2.08 m³/h: 1.2...552 gph: 0.02...9.2 gpm
Analogue start point ASP
0...28 l/min: 0...1.7 m³/h: 0...666 gph: 0...7.4 gpm
Analogue end point AEP
7...35 l/min: 0.42...2.1 m³/h: 111...555 gph: 1.85...9.25 gpm
Low flow cut-off LFC
0.05...1.75 l/min: 0.003...0.1 m³/h: 0.6...27.6 gph: 0.01...0.46 gpm
Frequency end point, FEP
7...35 l/min: 0.42...2.1 m³/h: 111.6...555 gph: 1.86...9.25 gpm
Frequency at the end point FRP [Hz]
1...10000
Pulse length [s]
0.001...2
Pulse value
0.001...99990000 I
Measuring range [°F]
-4...194
Display range [°F]
-43.6...233.6
Resolution [°F]
0.1
Set point SP [°F]
-3.3...194
Reset point rP [°F]
-4...193.3
Analogue start point [°F]
-4...154.4
Analogue end point [°F]
35.6...194
In steps of [°F]
0.1
Accuracy (in the measuring range)
± (0,8 % MW + 0,2 % MEW)
Repeatability
± 0,2 % MEW
Accuracy [K]
± 2,5 (Q > 5 % MEW)
Start-up delay [s]
0...50
Response time [s]
< 0.25; (dAP = 0, T09)
Damping process value dAP [s]
0...5
Response time [s]
15; (Q > 10 % MEW, T09)
Parameter setting options
hysteresis / window; normally open / normally closed; switching logic; frequency output; current/pulse output; start-up delay; display can be deactivated; Display unit
Communication interface
IO-Link
Transmission type
COM2 (38,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9
Profiles
Common - I&D: Identification and Diagnosis; Function: Measurement data, standard resolution
SIO mode
Yes
Required master port type
A
Process data analogue
3
Process data binary
2
Min. process cycle time [ms]
8
Supported DeviceIDs
Type of operation: DeviceID; default: 952
Ambient temperature [°F]
-4...140
Storage temperature [°F]
-13...176
Protection rating
IP 65; IP 67
EMC
DIN EN 60947-5-9
Shock resistance
DIN IEC 68-2-27: 20 g (11 ms)
Vibration resistance
DIN IEC 68-2-6:: 5 g (10...2000 Hz)
MTTF [years]
114
UL approval
UL approval no.: I014; File number UL: E174189
Pressure Equipment Directive
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight [g]
817.55
Housing
rectangular
Dimensions [mm]
110 x 48 x 73
Materials
stainless steel (316/1.4408); stainless steel (316L/1.4404); PC; PBT+PC-GF30
Report a product information error
Documents and technical resources
ARAN VISION product sheetView and print specifications
Manufacturer datasheetOpen manufacturer datasheet
Official product pageifm

Source checked: 2026-09-11

Product questions

Send the part number and your question to support to check compatibility, lead time or specifications.

Additional information and order matching

The revision, condition, delivery time and required documentation must be confirmed before the order is finalised. Export classifications and approvals are provided only where valid evidence is available.

Authenticity and condition

Product authenticity and actual condition, including new condition when offered as new, are checked before final approval and recorded in the quotation.

Matching technical version

The part number, revision, firmware or version is checked against your requirements. Apparently similar products may differ in price because of their version or condition.

Delivery estimate before ordering

Specialist products have a lead time. The valid delivery estimate is stated in the quotation after checking availability and specifications.

Technical code verification

Model, revision and equipment compatibility are checked before final confirmation.

Clear product condition

New, surplus or refurbished condition and warranty terms are stated in the quotation.

Products outside the catalog

If this model is unavailable, send the part number or nameplate photo for custom sourcing.

Related products