ARAN VISIONAccountQuote basketفارسی

ifm PN7094

ifm PN7094
Manufacturer
ifm
Manufacturer part number
PN7094
Description
Pressure sensor with display, PN-010-RER14-QFRKG/US/ /V
Manufacturer standard lead time
Manufacturer confirmation required; not a guaranteed delivery date.

Product specifications

Number of inputs and outputs
Number of digital outputs: 2
Measuring range
-1...10 bar: -14.5...145 psi: -0.1...1 MPa
Process connection
threaded connection G 1/4 internal thread
Special feature
Gold-plated contacts
Measuring element
ceramic-capacitive pressure measuring cell
Application
for industrial applications
Media
liquids and gases
Medium temperature [°C]
-25...80
Min. burst pressure
150 bar: 2175 psi: 15 MPa
Pressure rating
75 bar: 1087 psi: 7.5 MPa
Vacuum resistance
-1000 mbar: -0.1 MPa
Type of pressure
relative pressure; vacuum
Operating voltage [V]
18...30 DC; (to SELV/PELV)
Current consumption [mA]
< 35
Min. insulation resistance [MΩ]
100; (500 V DC)
Protection class
III
Reverse polarity protection
yes
Power-on delay time [s]
< 0.3
Integrated watchdog
yes
Total number of outputs
2
Output signal
switching signal; IO-Link; (configurable)
Electrical design
PNP/NPN
Number of digital outputs
2
Output function
normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]
2.5
Permanent current rating of switching output DC [mA]
150; (200 (...60 °C) 250 (...40 °C))
Switching frequency DC [Hz]
< 170
Short-circuit protection
yes
Type of short-circuit protection
pulsed
Overload protection
yes
Set point SP
-0.9...10 bar: -13.5...145 psi: -0.09...1 MPa
Reset point rP
-0.95...9.95 bar: -14...144.5 psi: -0.095...0.995 MPa
Min. difference between SP and rP
0.05 bar: 1 psi: 0.005 MPa
In steps of
0.05 bar: 0.5 psi: 0.005 MPa
Set point SP
-0.92...10 bar: -13.3...145 psi: -0.092...1 MPa
Reset point rP
-0.97...9.95 bar: -14...144.3 psi: -0.097...0.995 MPa
Min. difference between SP and rP
0.05 bar: 0.8 psi: 0.005 MPa
In steps of
0.01 bar: 0.1 psi: 0.001 MPa
Switch point accuracy [% of the span]
< ± 0,5
Repeatability [% of the span]
< ± 0,1; (with temperature fluctuations < 10 K)
Characteristics deviation [% of the span]
< ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation [% of the span]
< ± 0,25
Long-term stability [% of the span]
< ± 0,05; (per 6 months)
Temperature coefficient zero point [% of the span / 10 K]
< ± 0,2; (0...80 °C)
Temperature coefficient span [% of the span / 10 K]
< ± 0,2; (0...80 °C)
Response time [ms]
< 3
Delay time programmable dS, dr [s]
0...50
Parameter setting options
hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping; Display unit
Communication interface
IO-Link
Transmission type
COM2 (38,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9
SIO mode
yes
Required master port type
A; (when pin 2 not connected: B)
Supported DeviceIDs
Type of operation: DeviceID; Factory setting / CMPT = 2: 403; Status_B High Resolution / CMPT = 3: 601
Note
For further information please see the IODD PDF file under "Downloads"
Profiles
Smart Sensor - SSP 0: Generic Profiled Sensor; Function: Device identification; Function: Process data variable; Function: Device diagnosis
Min. process cycle time [ms]
2.3
IO-Link resolution pressure
0.01 bar: 0.001 MPa
IO-Link process data (cyclical)
function: bit length; pressure: 14; binary switching information: 2
IO-Link functions (acyclical)
application specific tag
Profiles
Smart Sensor - SSP 3.1: Measuring Sensor; Common - I&D: Identification and Diagnosis
Min. process cycle time [ms]
3
IO-Link resolution pressure
0.005 bar: 0.0005 MPa
IO-Link process data (cyclical)
function: bit length; pressure: 16; device status: 4; binary switching information: 2
Ambient temperature [°C]
-25...80
Storage temperature [°C]
-40...100
Protection
IP 65; IP 67
EMC
DIN EN 61000-6-2; DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-27: 50 g (11 ms)
Vibration resistance
DIN EN 60068-2-6: 20 g (10...2000 Hz)
MTTF [years]
260
UL approval
UL approval no.: J001
Pressure Equipment Directive
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight [g]
241.7
Housing
cylindrical
Dimensions [mm]
Ø 34 / L = 90.7
Materials
stainless steel (316L/1.4404); PBT+PC-GF30; PBT-GF20; PC
Materials (wetted parts)
stainless steel (316L/1.4404); ceramics; FKM
Min. pressure cycles
100 million

Documents and media

Price and availability

Checking member pricing…

Supply, condition, exact revision and delivery are confirmed before accepting the order. Catalog presence does not mean local stock.