Manufacturer part number
BMEAHO0412C
Brand
Schneider Electric
Category
PLC and HMI
Catalog status
Request a quotation

Technical specifications

Controller family
Modicon X80
Signal direction
Output
Analog channels
4
Signal range
4–20 mA
Connection
20-way removable terminal block
Variant identity
Dedicated severe-environment ordering reference; retain exact H or C suffix
Document pages
106
Operating temperature
−25…+60 °C
HART protocols
Versions5,6,7; point-to-point topology
Resolution
15 bits + sign
Rack requirement
Main BMEXBP Ethernet rack with compatible BMEP58 CPU or main RIO rack with BMECRA31210; no rack-extension installation. M580 Hot Standby local-I/O ban still applies.
Nominal signal range
4–20 mA
Maximum conversion range
0–21 mA; not the nominal output range
Internal buffer refresh time
2 ms; PLC scan and HART response add to overall application timing
Manufacturer technical catalog · DIA6ED2131203EN; exact ordering table PDF106 · en · PDF · DIA6ED2131203EN · 2025-01Manufacturer source: Schneider Electric · Model explicitly covered in family document · Covered models: BMEAHO0412C · Checked: 2026-10-23Manufacturer manual · EAV16400.10; exact model and architecture PDF12,43,44,45 · en · PDF · EAV16400.10 · 2023-11Manufacturer source: Schneider Electric · Model explicitly covered in family document · Covered models: BMEAHO0412C · Checked: 2026-10-23Official manufacturer source

This sheet provides a quick technical summary. For design, installation and final selection, review the latest official manufacturer documentation and verify the complete part number.