ARAN VISION
Product specification sheet
CPX-AP-I-PN-M12Document: AV-FESTO-8086607
Festo
CPX-AP-I-PN-M12Product image is not available.Festo · Industrial networking
Industrial PROFINET interface Festo CPX-AP-I-PN-M12
PROFINET interface for CPX-AP-I; module compatibility, power budgeting and network configuration require review against the project documentation.
- Manufacturer part number
CPX-AP-I-PN-M12- Brand
- Festo
- Category
- Industrial networking
- Catalog status
- Request a quotation
Technical specifications
- Manufacturer order number
- 8086607
- Fieldbus protocols
- PROFINET IRT / PROFINET RT
- Transmission rate
- 100 Mbit/s
- Maximum modules
- 80
- Maximum address volume
- 1024 bytes inputs / 1024 bytes outputs
- Configuration
- GSDML file
- Nominal operating voltage
- 24 V DC ±25%; load and electronics/sensors; SELV/PELV required; account for voltage drop
- Maximum supply current
- 2 × 4 A; external fuse required
- Fieldbus connection
- 2 × M12 D-coded sockets
- System communication
- AP; M8 D-coded; maximum cable length 50 m with nominal supply voltage
- Degree of protection
- IP65 / IP67; unused connections must be sealed
- Ambient temperature
- -20–60 °C
- Manufacturer document edition
- Printed date: 8/11/26; date format not resolved
This sheet provides a quick technical summary. For design, installation and final selection, review the latest official manufacturer documentation and verify the complete part number.