ARAN VISION
Product specification sheet
6ES71556AR000AN0Document: AV-FEED-1OEOEN4

Siemens · PLC and HMI
Industrial communication module Siemens model 6ES71556AR000AN0
Industrial communication module Siemens part number 6ES71556AR000AN0; Rated value (DC): 24 V; permissible range, lower limit (DC): 19.2 V; permissible range, upper limit (DC): 28.8 V. Technical specifications, condition and supply feasibility are checked before ordering.
- Manufacturer part number
6ES71556AR000AN0- Brand
- Siemens
- Category
- PLC and HMI
- Catalog status
- Request a quotation
Technical specifications
- Product type designation
- IM 155-6 PN BA
- PROFINET from GSD version/GSD revision
- GSDML V2.31
- Rated value (DC)
- 24 V
- permissible range, lower limit (DC)
- 19.2 V
- permissible range, upper limit (DC)
- 28.8 V
- Number of PROFINET interfaces
- 1; 2 ports (switch)
- RJ 45 (Ethernet)
- Yes; 2 integrated RJ45 ports
- BusAdapter (PROFINET)
- No
- PROFINET IO device
- Yes
- Open IE communication
- Yes
- Media redundancy
- Yes; PROFINET MRP client
- Transmission procedure
- PROFINET with 100 Mbit/s full duplex (100BASE-TX)
- PROFINET IO
- Yes
- PROFIBUS
- No
- EtherNet/IP
- No
- PROFINET system redundancy (S2)
- No
- Monitoring of the supply voltage (PWR-LED)
- Yes; green PWR LED
- between PROFINET and all other circuits
- Yes; 1500 V AC (type test)
- Width
- 35 mm
- Height
- 117 mm
- Depth
- 74 mm
- HW functional status
- from FS04
- FW update possible
- Yes
- I&M data
- Yes; I&M0 to I&M3
- Module swapping during operation (hot swapping)
- Yes; Single hot swapping
- Isochronous mode
- No
- STEP 7 TIA Portal configurable/integrated from version
- V13 SP1
- STEP 7 configurable/integrated from version
- V5.5 SP4
- via dataset
- Yes
- Reverse polarity protection
- Yes
- Short-circuit protection
- Yes
- Mains/voltage failure stored energy time
- 5 ms
- Current consumption, max.
- 300 mA
- I²t
- 0.09 A²·s
- Power loss, typ.
- 1.8 W
- Address space per module, max.
- 32 byte; For input and output data respectively
- Supports protocol for PROFINET IO
- Yes
This sheet provides a quick technical summary. For design, installation and final selection, review the latest official manufacturer documentation and verify the complete part number.