ARAN VISION logo

ARAN VISION

Product specification sheet

6EP19612BA11Document: AV-FEED-OTEG9P
Industrial I/O module Siemens model 6EP19612BA11,  Part number 6EP19612BA11

Siemens · PLC and HMI

Industrial I/O module Siemens model 6EP19612BA11

Industrial I/O module Siemens part number 6EP19612BA11; supply voltage at DC rated value: 24 V; type of current supply: Selectivity module, 4 x 3 A Common signal contact; type of the power supply network: Controlled DC voltage. Technical specifications, condition and supply feasibility are checked before ordering.

Manufacturer part number
6EP19612BA11
Brand
Siemens
Category
PLC and HMI
Catalog status
Request a quotation

Technical specifications

product type designation
PSE200U
supply voltage at DC rated value
24 V
type of outputs connection
simultaneous switch-on of all outputs after power-up of the supply voltage > 20 V, delay time of 25 ms, 100 ms, or "load-optimized" via DIP switch configurable for sequential switch-on
protection class IP
IP20
width × height × depth of the enclosure
72 × 80 × 72 mm
installation width × mounting height
72 mm × 180 mm
DIN-rail mounting
Yes
S7 rail mounting
No
net weight
0.2 kg
Technical Product Detail Page
https://i.siemens.com/1P6EP1961-2BA11
product brand name
SITOP
product designation
SITOP Selectivity module
type of current supply
Selectivity module, 4 x 3 A Common signal contact
type of the power supply network
Controlled DC voltage
input voltage at DC
22 ... 30 V
overvoltage overload capability
35 V
input current at rated input voltage 24 V rated value
12 A
voltage curve at output
controlled DC voltage
formula for output voltage
Vin - approx. 0.2 V
relative overall tolerance of the voltage note
In accordance with the supplying input voltage
number of outputs
4
output current up to 60 °C per output rated value
3 A
adjustable current response value current of the current-dependent overload release
0.5 ... 3 A
type of response value setting
via potentiometer
response delay maximum
5 s
product feature parallel switching of outputs
No
efficiency in percent
97 %
power loss [W] at rated output voltage for rated value of the output current typical
9 W
of the excess current
Iout = 1.0 ...1.5 x set value, switch-off after approx. 5 s
of the current limitation
Iout = 1.5 x set value, switch-off after typ. 100 ms
of the immediate switch-off
Iout > set value and Vin < 20 V, switch-off after approx. 0.5 ms
residual current at switch-off typical
1 mA
design of the reset device/resetting mechanism
via sensor per output
remote reset function
non-isolated 24 V input (signal level "high" at > 15 V)
fuse protection type at input
5 A per output (not accessible)
display version for normal operation
Three-color LED per output: green LED for "Output switched through"; yellow LED for "Output switched off manually"; red LED for "Output switched off due to overcurrent"

This sheet provides a quick technical summary. For design, installation and final selection, review the latest official manufacturer documentation and verify the complete part number.