Specialist electrical and industrial automation store
فارسی

PROFIsafe and IO-Link safety I/O module ifm model AL200S

PROFIsafe and IO-Link safety I/O module ifm model AL200S,  Part number AL200S

Check the part number and technical specifications before selection; an image alone is not sufficient for matching.

Manufacturer part number
AL200S
Manufacturer
ifm
ARAN VISION part number
AV-FEED-5FX8NY
Product description
PROFIsafe and IO-Link safety I/O module ifm part number AL200S; Design: only for operation with IO-Link masters AL140x, AL1304 to AL1307 and Siemens PLCs S7-1200 and S7-1500 (except software controller and open controller); Application: I/O modules for field applications; Operating voltage [V]: 19.2...30.2 DC; (US ; to SELV/PELV). Technical specifications, condition and supply feasibility are checked before ordering.
Manufacturer standard lead time
Manufacturer confirmation required

Manufacturer replenishment time; delivery to you is confirmed separately.

Product attributes

Design
only for operation with IO-Link masters AL140x, AL1304 to AL1307 and Siemens PLCs S7-1200 and S7-1500 (except software controller and open controller)
Application
I/O modules for field applications
Operating voltage [V]
19.2...30.2 DC; (US ; to SELV/PELV)
Current consumption [mA]
67; (US)
Protection class
III
Additional voltage supply [V]
19.2...30.2 DC; (UA)
Max. current consumption from additional supply [mA]
34; (UA)
Max. current load total [A]
6
Current rating per port [A]
2
Total number of inputs and outputs
12
Total number of inputs
8
Switching level high [V]
11...30
Switching level low [V]
-30...5
Digital inputs protected against short circuits
Yes
Total number of outputs
4
Short-circuit proof
Yes
Communication interface
IO-Link
Supported DeviceIDs
Type of operation: DeviceID; IO-Link Device: 1312
Transmission type
COM3 (230,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9
Profiles
Function: Extended identification
SIO mode
No
Min. process cycle time [ms]
4
Ambient temperature [°C]
-25...60
Storage temperature [°C]
-40...85
Max. relative air humidity [%]
75
Protection
IP 65; IP 67
EMC
EN 61000-6-2; EN 61000-4-2 ESD: 6 kV CD / 8 kV AD; EN 61000-4-3 HF radiated: 10 V/m; EN 61000-4-4 Burst: 2 kV; EN 61000-4-5 Surge; EN 61000-4-6 HF conducted
Shock resistance
DIN EN 60068-2-27
Vibration resistance
DIN EN 60068-2-64 2009-04; DIN EN 60068-2-6 2008-10
Mission time TM [h]
175200
Mission time TM (additional indication)
20 years
Complies with the requirements
ISO 13849-1 PL d; IEC 61508 SIL 2; IEC 62061 SIL 2
PFH [1/h]
1E-08
PFD
1E-04
Complies with the requirements
ISO 13849-1 PL e; IEC 61508 SIL 3; IEC 62061 SIL 3
PFH [1/h]
1E-09
PFD
1E-05
Weight [g]
408.3
Housing
rectangular
Type of mounting
backplane mounting
Dimensions [mm]
214 x 59.8 x 30
Materials
housing: PA; socket: brass nickel-plated
Remarks
Safety classification depends on parameter setting and wiring (see operating instructions).
Pack quantity
1 pcs.
Connector
M12; coding: A; Contacts: 5
Connector
M12; coding: L; Contacts: 5
Report a product information error
Documents and technical resources
ARAN VISION product sheetView and print specifications
Official product pageifm

Source checked: 2026-09-10

Product questions

Send the part number and your question to support to check compatibility, lead time or specifications.

Additional information and order matching

The revision, condition, delivery time and required documentation must be confirmed before the order is finalised. Export classifications and approvals are provided only where valid evidence is available.

Authenticity and condition

Product authenticity and actual condition, including new condition when offered as new, are checked before final approval and recorded in the quotation.

Matching technical version

The part number, revision, firmware or version is checked against your requirements. Apparently similar products may differ in price because of their version or condition.

Delivery estimate before ordering

Specialist products have a lead time. The valid delivery estimate is stated in the quotation after checking availability and specifications.

Technical code verification

Model, revision and equipment compatibility are checked before final confirmation.

Clear product condition

New, surplus or refurbished condition and warranty terms are stated in the quotation.

Products outside the catalog

If this model is unavailable, send the part number or nameplate photo for custom sourcing.