ifmAL200S

PROFIsafe and IO-Link safety I/O module ifm model AL200S

PROFIsafe and IO-Link safety I/O module ifm model AL200S,  Part number AL200S

Verify the part number and specifications; the image alone does not establish suitability.

ARAN VISION reference
AV-FEED-5FX8NY
Manufacturer sourcing lead time
Manufacturer confirmation required

Delivery to your location is confirmed separately.

Documents / datasheets
ARAN VISION specification sheet

Technical specifications

Design
only for operation with IO-Link masters AL140x, AL1304 to AL1307 and Siemens PLCs S7-1200 and S7-1500 (except software controller and open controller)
Application
I/O modules for field applications
Operating voltage [V]
19.2...30.2 DC; (US ; to SELV/PELV)
Current consumption [mA]
67; (US)
Protection class
III
Additional voltage supply [V]
19.2...30.2 DC; (UA)
Max. current consumption from additional supply [mA]
34; (UA)
Max. current load total [A]
6
Current rating per port [A]
2
Total number of inputs and outputs
12
Total number of inputs
8
Switching level high [V]
11...30
Switching level low [V]
-30...5
Digital inputs protected against short circuits
Yes
Total number of outputs
4
Short-circuit proof
Yes
Communication interface
IO-Link
Supported DeviceIDs
Type of operation: DeviceID; IO-Link Device: 1312
Transmission type
COM3 (230,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9
Profiles
Function: Extended identification
SIO mode
No
Min. process cycle time [ms]
4
Ambient temperature [°C]
-25...60
Storage temperature [°C]
-40...85
Max. relative air humidity [%]
75
Protection rating
IP 65; IP 67
EMC
EN 61000-6-2; EN 61000-4-2 ESD: 6 kV CD / 8 kV AD; EN 61000-4-3 HF radiated: 10 V/m; EN 61000-4-4 Burst: 2 kV; EN 61000-4-5 Surge; EN 61000-4-6 HF conducted
Shock resistance
DIN EN 60068-2-27
Vibration resistance
DIN EN 60068-2-64 2009-04; DIN EN 60068-2-6 2008-10
Mission time TM [h]
175200
Mission time TM (additional indication)
20 years
Complies with the requirements
ISO 13849-1 PL e; IEC 61508 SIL 3; IEC 62061 SIL 3
PFH [1/h]
1E-09
PFD
1E-05
Weight [g]
408.3
Housing
rectangular
Type of mounting
backplane mounting
Dimensions [mm]
214 x 59.8 x 30
Materials
housing: PA; socket: brass nickel-plated
Remarks
Safety classification depends on parameter setting and wiring (see operating instructions).
Pack quantity
1 pcs.
Connector
M12; coding: L; Contacts: 5
Report a product-data issue

Documents / datasheets

Source reviewed: 2026-10-24

Description

PROFIsafe and IO-Link safety I/O module ifm part number AL200S; Operating voltage [V]: 19.2...30.2 DC; (US ; to SELV/PELV); Current consumption [mA]: 67; (US); Additional voltage supply [V]: 19.2...30.2 DC; (UA). Technical specifications, condition and supply feasibility are checked before ordering.

Ask about this product

Send the part number and your question for technical or sourcing review.

Condition and order verification

Authenticity and condition

Product authenticity and actual condition, including new condition when offered as new, are checked before final approval and recorded in the quotation.

Matching technical version

The part number, revision, firmware or version is checked against your requirements. Apparently similar products may differ in price because of their version or condition.

Delivery estimate before ordering

Specialist products have a lead time. The valid delivery estimate is stated in the quotation after checking availability and specifications.