نشان ARAN VISION

ARAN VISION

Datasheet فنی محصول

5069-IY4Document: AV-FEED-134JZT5
Temperature and thermocouple module Allen-Bradley model 5069-IY4,  Part number 5069-IY4

Allen-Bradley · PLC and HMI

Temperature and thermocouple module Allen-Bradley model 5069-IY4

Temperature and thermocouple module Allen-Bradley part number 5069-IY4; Lifecycle Status: Active; Repair Options Available: No; Number Of Channels: 4 Channel. Technical specifications, condition and supply feasibility are checked before ordering.

Manufacturer part number
5069-IY4
Brand
Allen-Bradley
Category
PLC and HMI
Status فهرست
Available on request

Specifications فنی

Lifecycle Status
Active
Repair Options Available
No
Number Of Channels
4 Channel
Output Signal
Analog
Accuracy drift with temperature
Voltage: 0.200% full scale, Current: 0.300% full scale, RTD: 0.200% full scale, Thermocouple/mvolt: 0.200% full scale
Analogue inputs configurable
true
Analogue outputs configurable
false
Calibrated accuracy
Voltage: 0.100% full scale @ 25 °C Current: 0.100% full scale @ 25 °C RTD: 0.100% full scale @ 25 °C Thermocouple/mvolt: 0.100% full scale @ 25 °C
Calibration methods
Factory calibrated, User-performed (optional)
CJC inputs
Two CJC sensors, 2 thermistors embedded in 5069-RTB14CJC-(screw or spring) RTB, -or- 2 thermistors wired to 5069-RTB18-(screw or spring) RTB, Thermistor type: Measurement specialties, Inc. 10K3A1A, (for thermocouple mode use only)
Common mode noise rejection ratio
130 dB @ 50/60 Hz
Common mode voltage
±10V (Current mode and 3-wire RTD mode), ±2V (Voltage mode)
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Data format
IEEE 32-bit floating point
Data value during overload condition
Full scale, overrange flag, Data uncertain / data bad
Depth
105.42 mm
DIN rail
Compatible zinc-plated chromate-passivated steel DIN rail, You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in)
EFT/B immunity
±4kV @ 5kHz on power ports, ±3kV @ 5kHz on shielded input ports
Emissions
IEC 61000-6-4
Enclosure type
None (open-style)
ESD immunity
6 kV contact discharges, 8 kV air discharges
HART handheld compliance
Add an external 250 Ω resistor into the current loop for HART transmitter compliance
Height
144.57 mm
Indicators
1 green/red module status indicator, 4 yellow/red I/O status indicators, 2 yellow/red CJC status indicators
Input anti-aliasing filter cutoff frequency, typical
500 Hz
Input, current
true
Input digital filter
First order lag, 0 ms…32,767 ms (32.767 s)
Input impedance
Voltage: >1 MΩ, Current: 90 Ω typical, 70…110 Ω range, RTD: >1 MΩ, Thermocouple/mvolt: >1 MΩ
Input notch filter (Hz) selections
5, 10 (50/60 default), 15, 20, 50, 60, 100, 200, 500, 1000, 2500, 5000, 10000, 15625, 25000, 31250, 62500
Input range, current
0...20mA @ 4....20mA
Input range, resistive
1...500 Ω, 2...1000 Ω, 4...2000 Ω, 8...4000 Ω
Input range, thermocouple / millivolt
±100 mV
Input range, voltage
±10V @ 0...10V, 0...5V
Input, resistance thermometer
true
Input, resistor
true
Inputs
4 differential

این برگه, خلاصه فارسی Specifications محصول for Quick links است. for طراحی, Mounting and انتخاب نهایی, آخرین Official manufacturer documentation and تطابق Complete Part number بررسی شود.