ARAN VISION logo

ARAN VISION

Product specification sheet

5069-AENTRDocument: AV-FEED-1B4FYQH
Industrial network adapter and scanner Allen-Bradley model 5069-AENTR,  Part number 5069-AENTR

Allen-Bradley · Industrial networking

Industrial network adapter and scanner Allen-Bradley model 5069-AENTR

Industrial network adapter and scanner Allen-Bradley part number 5069-AENTR; Isolation voltage: 250V (continuous), basic insulation type, SA, and MOD power to backplane, 250V (continuous), basic insulation type, SA to MOD power, 250V (continuous), basic insulation type, Ethernet to backplane, type tested at 1500V AC @ 60s, 250V (continuous), doub; MOD power: 220mA @ 18...32V DC; MOD Power inrush: 1750 mA for 70 ms. Technical specifications, condition and supply feasibility are checked before ordering.

Manufacturer part number
5069-AENTR
Brand
Allen-Bradley
Category
Industrial networking
Catalog status
Available on request

Technical specifications

Lifecycle Status
Active
Repair Options Available
No
Depth
105 mm
Height
138 mm
Isolation
300V(cont);No isolation
ATEX temp code
T4
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on power and Ethernet ports
EFT/B immunity
±3kV @ 5kHz on power ports, ±3kV @ 5kHz on Ethernet ports
Emissions
CISPR 11/22, Class A
Enclosure type rating
None (open-style)
ESD immunity
6 kV contact discharges, 8 kV air discharges
Insulation stripping length
5069-RTB5-SPRING connections: 10 mm (0.39 in.), 5069-RTB5-SCREW connections: 10 mm (0.39 in.)
IO link master
false
Isolation voltage
250V (continuous), basic insulation type, SA, and MOD power to backplane, 250V (continuous), basic insulation type, SA to MOD power, 250V (continuous), basic insulation type, Ethernet to backplane, type tested at 1500V AC @ 60s, 250V (continuous), doub
MOD power
220mA @ 18...32V DC
MOD Power inrush
1750 mA for 70 ms
MOD power passthrough, max
9.78A @ 18...32V DC, Maximum level of MOD Power current that the adapter can pass through to the next module in the system
Module keying
Electronic keying via progming software
Nonoperating temperature
-40 °C
Number of HW-interfaces industrial Ethernet
1
Operating temperature
0 °C <Ta <60 °C (32 °F <Ta <140 °F)
Power dissipation, max
8.5 W
Radiated RF immunity
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz, 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz, 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Recommended external overcurrent protection
MOD power: 10...12A @ 22.5...43.2A2t, fast acting, SA power: 20A @ 250V AC
Redundancy
false
Relative humidity
5...95% noncondensing
RTB keying
None
RTB torque
0.5...0.6 Nm (4.4...5.3 in-lb), (5069-RTB5-SCREW RTB only)
SA power
5mA @ 0...32V DC, 2mA @ 0...240V AC, 47...63 Hz, ATEX/IECEx, 125V AC maximum
SA power passthrough, max
9.95A @ 0...32V DC, 9.975A @ 0...240V AC, 47...63 Hz, ATEX/IECEx, 125V AC maximum, Maximum level of SA power current that the adapter can pass through to the next module in the system
Shock
Operating: 30 G, Non operating: 50 G
Supporting protocol for ASI
false
Supporting protocol for AS-Interface Safety at Work
false
Supporting protocol for CAN
false

This sheet provides a quick technical summary. For design, installation and final selection, review the latest official manufacturer documentation and verify the complete part number.