ARAN VISION logo

ARAN VISION

Product specification sheet

1756-OF8IDocument: AV-FEED-TL8VME
Analog I/O module Allen-Bradley model 1756-OF8I,  Part number 1756-OF8I

Allen-Bradley · PLC and HMI

Analog I/O module Allen-Bradley model 1756-OF8I

Analog I/O module Allen-Bradley part number 1756-OF8I; Current draw: 200mA @ 5.1V, Voltage or current mode with 250 Ω loads = 220mA @ 24V, Current mode with 500 Ω loads = 275mA @ 24V, Current mode with 750 Ω loads = 340mA @ 24V, Current mode with 1000 Ω loads = 385mA @ 24V; Input, current: true; Input signal, configurable: true. Technical specifications, condition and supply feasibility are checked before ordering.

Manufacturer part number
1756-OF8I
Brand
Allen-Bradley
Category
PLC and HMI
Catalog status
Available on request

Technical specifications

Lifecycle Status
Active
Repair Options Available
Yes
Display
Module Health, In Calibration,Mode, Input, Fault and,Communication Status
Isolation
250V (continuous), reinforced,insulation type, outputs to,backplane. 250V (continuous),basic insulation type, output,to output
Special Features
Per Point Isolation
Analogue inputs configurable
true
Analogue outputs configurable
false
Calibrated accuracy
0.05% @ 25°C (77 °F)
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Current draw
200mA @ 5.1V, Voltage or current mode with 250 Ω loads = 220mA @ 24V, Current mode with 500 Ω loads = 275mA @ 24V, Current mode with 750 Ω loads = 340mA @ 24V, Current mode with 1000 Ω loads = 385mA @ 24V
Data format
IEEE 32-bit floating point
Drive capability
Current output = 0...1000 Ω, Voltage output =>1000 Ω
EFT/B immunity
±4kV @ 5kHz on signal ports
Emissions
IEC 61000-6-4
Enclosure type rating
None (open-style)
ESD immunity
6 kV contact discharges, 8 kV air discharges
Input, current
true
Input, resistance thermometer
false
Input, resistor
false
Number of Inputs and Type
Eight isolated channels - any combination of voltage or current mode
Input signal, configurable
true
Input, thermocouple
false
Input, voltage
true
Isolation voltage
250V (continuous), reinforced insulation type, outputs to backplane, 250V (continuous), basic insulation type, output to output
Module conversion method
R-Ladder DAC, monotonicity with no missing codes
Module error over full temperature range
0.1 %
Module keying
Electronic, software configurable
Module scan time
1 ms minimum
Nonoperating temperature
-40 °C
North American temperature code
T4
Open circuit detection
Current output = Yes
Operating temperature
0 to 60 °C
Output, current
false
Output impedance
46 Ω (Current output)
Output range
-10…10V, 0…10V, 0…5V, 0…20 Ma
Output signal configurable
false

This sheet provides a quick technical summary. For design, installation and final selection, review the latest official manufacturer documentation and verify the complete part number.