Analog I/O module Allen-Bradley model 1756-OF8H,  Part number 1756-OF8H

Allen-Bradley · PLC and HMI

Analog I/O module Allen-Bradley model 1756-OF8H

Analog I/O module Allen-Bradley part number 1756-OF8H; Lifecycle Status: Active; Repair Options Available: Yes; Display: Module Health, In Calibration,Mode. Technical specifications, condition and supply feasibility are checked before ordering.

Manufacturer part number
1756-OF8H
Brand
Allen-Bradley
Category
PLC and HMI
Status فهرست
Available on request

Specifications فنی

Lifecycle Status
Active
Repair Options Available
Yes
Display
Module Health, In Calibration,Mode
Isolation
None between channels (Single,Ended)
Number Of Channels
8
Output Signal
+/- 10.4V, 0-20 mA, 4-20 mA
Special Features
Supports HART Protocol
Analogue inputs configurable
true
Analogue outputs configurable
false
Calibrated accuracy
Voltage: Better than 0.1% of range @ 25 °C (77 °F) with HART disabled, Current: Better than 0.15% of range @ 25 °C (77 °F) with HART disabled
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
EFT/B immunity
±2kV @ 5kHz on signal ports
Emissions
IEC 61000-6-4
Enclosure type rating
None (open-style)
ESD immunity
6 kV contact discharges, 8 kV air discharges
Gain drift with temperature
Voltage: 20 ppm/°C, Current: 35 ppm/°C
Input conversion method
Successive approximation
Input, current
true
Input, resistance thermometer
false
Input, resistor
false
Input signal, configurable
true
Input, thermocouple
false
Input, voltage
true
Isolation voltage
50V (continuous), basic insulation type, output channels to backplane, No isolation between individual output channels type tested at 1500V AC @ 60s
Load reactance
Voltage: 1 µF, Current: 10 µH
Module error
Voltage: 0.15% of range, Current: 0.3% of range
Module HART scan time
Analog: 12 ms, minimum, floating point, HART: typically 1 s per HART channel enabled. Estimate 10 s if all 8 channels have HART enabled, Pass through messages, handheld communicators, sary masters, communication errors, or configuration changes can s
Module keying
Electronic, software configurable
Nonoperating temperature
-40 °C
North American temperature code
T4
Offset drift
100 µV/°C, 200 nA/°C
Open circuit detection time
Current output only (output must be set to <0.1 mA)
Operating temperature
0 °C <Ta <60 °C (32 °F <Ta <140 °F)
Output conversion method
R-Ladder DAC, monotonicity with no missing codes
Output, current
false