- ولتاژ کاری
- 18...30 DC
- Current consumption [mA]
- 100; (US)
- Protection class
- III
- Additional voltage supply [V]
- 18...30 DC; (UA)
- Max. current consumption from additional supply [mA]
- 3600; (UA)
- Total number of inputs and outputs
- 16
- Number of inputs and outputs
- Number of digital inputs: 16; Number of analogue inputs: 8; Number of digital outputs: 16
- تعداد ورودی دیجیتال
- 16; (configurable)
- Input circuit of digital inputs
- PNP; (type 3 (IEC 61131-2))
- Sensor supply of the inputs
- UA
- Voltage supply [V]
- 18...30
- Input current High [mA]
- 2...15
- Input current Low [mA]
- 0...1.5
- Switching level high [V]
- 11...28
- Switching level low [V]
- 0...5
- Number of analogue inputs
- 8; (configurable current/voltage input)
- Analogue input (current) [mA]
- 4...20
- Analogue input (voltage) [V]
- 0...10
- وضوح اندازهگیری
- 16 Bit
- تعداد خروجی دیجیتال
- 16; (configurable)
- Max. current load per output [mA]
- 1800
- Total current rating of all outputs [A]
- 3.6; (max. current load per segment: 1800 mA)
- حفاظت اتصال کوتاه
- دارد
- Actuator supply outputs
- UA
- رابط ارتباطی
- IO-Link
- Transmission type
- COM3 (230,4 kBaud)
- IO-Link revision
- 1.1
- SDCI standard
- IEC 61131-9
- Profiles
- Common - I&D: Identification and Diagnosis
- SIO mode
- ندارد
- Required master port type
- B
- Min. process cycle time [ms]
- 4
- Supported DeviceIDs
- Type of operation: DeviceID; Acyclic parametrisation: 1406; Factory setting: Cyclic parametrisation: 1405
- Note
- The parameter setting can be changed from cyclical to acyclical.; For further information please see the IODD PDF file under "Downloads"
- دمای محیط
- -25...60
- Storage temperature [°C]
- -25...70
- Max. relative air humidity [%]
- 90
- Max. height above sea level [m]
- 2000
- درجه حفاظت
- IP 65; IP 67; IP 69K; (operation with stainless steel protective caps: IP 69K)
- Protection rating (NEMA 250)
- 6P
- Pollution degree
- 2
- Chemical media
- ISO 16750-5: HLP, CC, DB, DC, DD, CA; NEMA 250 5.13.1: AA
- EMC
- EN 61000-6-2; EN 61000-6-4; IEC 61131-9
- Shock resistance
- DIN EN 60068-2-27
- Vibration resistance
- DIN EN 60068-2-64; DIN EN 60068-2-6
- MTTF [years]
- 40
- Weight [g]
- 398.7
- Housing
- rectangular
- Type of mounting
- backplane mounting
- Dimensions [mm]
- 208 x 59.3 x 38.4
- Materials
- housing: PA grey; socket: stainless steel (316L/1.4404)
- Sealing material
- EPDM
- Tightening torque [Nm]
- < 0.8
- Display
- operation: 1 x LED, green; fault: 1 x LED, red; function: 1 x LED, yellow
- Accessories (optional)
- protective cap for M12 sockets
- تعداد در بسته
- 1 pcs.
- Connector
- 8 x M12; coding: A; Contacts: 4; Sealing: EPDM
- Manufacturer device scope
- IO-Link input/output device, requiring a Class B master port; not an IO-Link master. COM3, minimum process cycle 4 ms; SIO mode not supported.
- Manufacturer I/O scope
- 16 total I/O; 16 digital input, 16 digital output and 8 analogue input capabilities depend on configuration, not 40 simultaneously available channels. Analogue input selectable 4–20 mA or 0–10 V, 16 bit.
- Manufacturer output scope
- 1.8 A maximum per output and per segment; 3.6 A total output current. Segment and total limits still apply; supply UA 18–30 V DC.
- DeviceID scope
- 1405 cyclic parameterisation is factory mode; 1406 is acyclic parameterisation. Verify IODD/device revision before commissioning.
- Manufacturer protection scope
- IP65 / IP67; IP69K operation requires stainless steel protective caps.