- کاربرد
- hygienic systems; I/O modules for field applications
- Loop-through function
- voltage supply; fieldbus interface; IoT interface
- ولتاژ کاری
- 20...28 DC; (US ; to PELV)
- Current consumption [mA]
- 300...3900; (US)
- Protection class
- III
- Additional voltage supply [V]
- 20...28 DC; (UA)
- Max. current load total [A]
- 3.6
- Current rating per port [A]
- 2
- Total number of inputs and outputs
- 16; (configurable)
- Number of inputs and outputs
- Number of digital inputs: 12; Number of digital outputs: 12
- تعداد ورودی دیجیتال
- 12; (IO-Link Port Class A: 4 x 2; IO-Link Port Class B: 4 x 1)
- Switching level high [V]
- 11...28
- Switching level low [V]
- 0...5
- تعداد خروجی دیجیتال
- 12; (IO-Link Port Class A: 4 x 1; IO-Link Port Class B: 4 x 2)
- Short-circuit proof
- دارد
- Max. current load per output [mA]
- 350
- Parameter setting options
- Node-RED
- سیستمعامل
- Embedded Linux
- رابط ارتباطی
- Ethernet; IO-Link
- Factory settings
- IP address: 169.254.x.x; subnet mask: 255.255.0.0; gateway IP address: 0.0.0.0; MAC address: see type label
- Transmission standard
- 100Base-TX
- نرخ انتقال
- 100 MBit/s
- پروتکل
- MQTT JSON; OPC UA
- Note on interfaces
- Secure protocol: HTTPS, MQTTS, TLS
- Transmission type
- COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud)
- IO-Link revision
- 1.1
- Number of ports class A
- 4
- Number of ports class B
- 4
- دمای محیط
- -25...60
- Storage temperature [°C]
- -25...85
- Max. relative air humidity [%]
- 90
- درجه حفاظت
- IP 65; IP 66; IP 67; IP 69K; (operation with stainless steel protective caps: IP 69K)
- Protection rating (NEMA 250)
- 6P
- Pollution degree
- 2
- Chemical media
- ISO 16750-5: HLP, CC, DB, DC, DD, CA; NEMA 250 5.13.1: AA
- EMC
- EN 61000-6-2; EN 61000-6-4
- Shock resistance
- DIN EN 60068-2-27
- Vibration resistance
- DIN EN 60068-2-64 2009-04; DIN EN 60068-2-6 2008-10
- MTTF [years]
- 38
- Weight [g]
- 649.55
- Housing
- rectangular
- Type of mounting
- backplane mounting
- Dimensions [mm]
- 238 x 74.3 x 24
- Materials
- housing: PA grey; socket: stainless steel (316L/1.4404)
- Sealing material
- EPDM
- Items supplied
- Protective cap: 1 x M12, stainless steel, E12542
- Remarks
- For further information please see the operating instructions.
- تعداد در بسته
- 1 pcs.
- Connector
- 1 x M12; coding: L; Contacts: 5; Sealing: EPDM
- Fieldbus protocol
- EtherNet/IP or PROFINET; factory setting EtherNet/IP.
- IoT protocol
- Independent IoT interface: MQTT JSON and OPC UA; secure protocols HTTPS, MQTTS and TLS.
- Manufacturer I/O scope
- 16 total configurable I/O; 12 digital inputs and 12 digital outputs are configuration capabilities, not 24 simultaneously available channels. Four Class A and four Class B ports. IP69K requires stainless steel protective caps.
- Sensor supply US scope
- 20–28 V DC; 3.6 A total; 2 A per port. Digital output current limit is separately 350 mA per US output; do not equate output and port supply ratings.
- Actuator supply UA scope
- 20–28 V DC; 4 A total and 4 A per port. Total limit still applies.
- Connector topology review scope
- Page 4: IO-Link connector header says Contacts 4 while Class B pin 5 is assigned UA minus; Ethernet header says 2 x M12 while XF1/XF2 and XI1/XI2 are listed. Connector topology and pin count require further verification.
- Housing depth review scope
- Drawing depth 40.9 mm and mechanical table 24 mm may refer to different envelopes; do not infer interchangeable housing depth.